Customization: | Available |
---|---|
Type: | Cabinet Air Conditioner |
Air Tube Material: | FRP |
Still deciding? Get samples of US$ 156/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Venttk Factory Directly! ! Roof Top Air Conditioners
We are a professional heat exchanger, condenser, evaporator, heat pump,air cooler and air conditioner manufacturer in China, which has more than 15 years experience in HVAC area. Our products have been exported to Europe,USA, Japan and Middle east etc.
water cooled package unit
water cooled package unit
Function
1. Two-way ventilation function: achieve two-way air exchange indoor and outdoor,take the outdoor fresh air into the room. While indoor polluted air let out the room,create new healthy green air-conditioning for you.
2. Efficient heat recovery efficiency of energy recovery can be built to complete the whole heat or sensible heat recovery, heat recovery efficiency of the whole is greater than 70%, significantly greater than 63% heat recovery efficiency, reduce energy consumption required for processing of fresh air for efficient energy saving.
3. Low Noise Design: built-in special low-noise air-conditioning fan, the machine housing wall covered with new sound-absorbing material, all quiet design, human embodiment of air conditioning super design.
4. Air filtration and purification functions: a coarse, medium and high efficiency filters available to prevent dust and other pollutants into the room, creating a clean environment.
Model | WRF12ZA | WRF 15ZA | WRF18ZA | WRF24ZA | WRF30ZA | WRF 35ZA | ||||
WF12ZA | WF 15ZA | WF18ZA | WF24ZA | WF30ZA | WF 35ZA | |||||
Cooling capacity | kW | 12 | 15.2 | 17.5 | 24 | 30.3 | 35.6 | |||
Heating capacity | kW | 13.2 | 16.6 | 18.4 | 26.5 | 33.3 | 37.7 | |||
Energy regulation |
% | 0,100% | 0,50,100% | |||||||
Power | 380V / 3Ph / 50HZA | |||||||||
Cooling input capacity | kW | 4.1 | 5.3 | 5.5 | 8.8 | 11.3 | 12.3 | |||
Heating input capacity | kW | 3.8 | 4.8 | 5.1 | 8.2 | 10.4 | 11.3 | |||
Start current | A | 48 | 62 | 63 | 63 | 74 | 76 | |||
Cooling running current | A | 7.4 | 9.7 | 10.2 | 16.1 | 21.2 | 23.3 | |||
Heating running current | A | 6.9 | 9.2 | 9.7 | 15.1 | 20.1 | 22.2 | |||
Throttling method |
Thermal expansion valve |
|||||||||
Cooling system | 1 | 1 | 1 | 1 | 2 | 2 | ||||
Refrigerant | R410A | |||||||||
Compressor | Compressor type | Hermetic scroll compressor |
||||||||
Qty | 1 | 1 | 1 | 1 | 2 | 2 | ||||
Condensation side |
||||||||||
Condenser | Type | Copper tube and aluminum fin | ||||||||
Qty | 1 | 1 | 1 | 1 | 1 | 1 | ||||
Drive type | Direct drive | |||||||||
Motor power | kW | 0.25 | 0.37 | 0.37 | 0.55 | 0.75 | 0.75 | |||
Air volume | m3 /h | 4600 | 7800 | 7800 | 9000 | 12600 | 12600 | |||
Evaporation side |
||||||||||
Evapotator | Type | Copper tube and aluminum fin | ||||||||
Qty | 1 | 1 | 1 | 1 | 1 | 1 | ||||
Motor power | kW | 0.32 | 0.37 | 0.45 | 1.1 | 1.5 | 2.2 | |||
Air volume | m3 /h | 2100 | 2600 | 3400 | 4100 | 5200 | 6300 | |||
Drive type | Direct drive | Pulley | ||||||||
Static pressure(Pa) | 100 | 100 | 100 | 200 | 200 | 250 | ||||
Filter | Aluminum filter G3 | |||||||||
Noise dB(A) | 67 | 67 | 68 | 71 | 72 | 72 | ||||
Refrigerant filling volume(kg) | 3.1 | 3.1 | 4.3 | 2x3.1 | 2x3.1 | 2x4.3 | ||||
External dimension | L | mm | 1410 | 1410 | 1410 | 1978 | 1978 | 1978 | ||
W | mm | 1100 | 1100 | 1100 | 1175 | 1175 | 1175 | |||
H | mm | 1095 | 1095 | 1095 | 1095 | 1095 | 1095 | |||
Weight | kg | 240 | 260 | 290 | 420 | 480 | 500 |