Glycol-Water Coolers for Heating Plants and Power Plants

Type: Air-Cooled
Cooling Water: Ethylene Glycol
System Type: Closed System
Fans Species: Single-speed Fan
Noise Level: Low
Application Fields: Industry
Customization:
Diamond Member Since 2010

Suppliers with verified business licenses

Manufacturer/Factory

Basic Info.

Model NO.
D2-250-6x630
Certification
ISO, SGS
Condition
New
Product
Air Cooler
Capacity
142.42kw
Air Flow
76459 M3/H
Fan
4* 630
Power
400/3n/50Hz
Fan Motor
20.4A
Sound Pressure Level
64dB(a)
Connections Inlet
2xdn50
Connections Onlet
2xdn50
Product Weight(Empty)
769kg
Transport Package
Export Packaging
Specification
811kg
Trademark
VENTTECH
Origin
Shanghai, China(Mainland)
HS Code
8415901000
Production Capacity
1500units Per Month

Product Description

Dry Cooler Features:
  1. High efficiency heat exchanger: capacity designs for maximizing the heat transfer relative to the energy consumption of the fan. Tube and tube coupling design for low pressure drop in the coil on the media sides(maximum 100KPa at water designing condition). Our thermodynamic and aerodynamic designing software is long year tested and proved in Germany
 
  1. Fan: only choose low specific energy consumption fans. Fan nozzle designs for maximum air flow and air throw.Our fans from the world`s leading manufacturer are practically proved to be reliable in operation and long lasting. Motor: protection class IP 54 and insulation class F. Air separator for each fan.
 
  1. We facilitate you to have a long lasting and low maintainance operation. Durable material and rigid enclosure with hard gloss powder coated finish. Protective enclosure for both manifolds and U-bends. Unit design for outdoor installation. 100% leakage tested at 31bar.
Model D2-250-6x630
Capacity Water KW 250.42
20% Et. Glycol KW 244.69
Air flow M3/h 111511
Fan No. X φ 2x3x630
Fan motor
400/3N/50HZ
A 30.6
Sound pressure level dB(A)10m 66
Dimension L mm 3250
H mm 1874
D mm 2100
D1 mm 2000
L1 mm 963
L2 mm 1000
L3 mm 2963
Connections inlet φ mm 2XDN80
Connections onlet φ mm 2XDN80
Product weight(empty) kg 1197
 
Dry Cooler Options:
1. Coil design refrigerant: water, oil, glycol.
2. 
Multiple circuits.
3. 
Sub-cooling circuits.
4. 
Stainless steel or aluminum casing.
5. 
Coated aluminum or copper fins.
6. 
Explosion ploof motor.
7. Customized fin spacing.


Dry cooler application:
Dry Coolers are widely used in refrigeration, air-conditioning, food processing, heating plants and power plants.
 

Dry cooler applicable environment:
1. Dry Cooler series:D1 and D2 series.
2. Environment temperature:  0ºC.
3. Air does not contain chemical substances, corrosive gasses and dust-free;
4. Please specify requirements for explosion-proof upon order
5. Design Conditions: Medium is water, Design pressure 2.0MPa ,Test pressure 2.5MPa
 
Common fault and treatment:
number Observation Possible cause Action
1 Fan not turning, noise or vibration when started Lack of phase or fan impeller blocked Eliminate blockage
2 Overheating Air inlet blocked or obstructed by foreign objects, impeller severely deformed or damaged, power supply voltage or frequency not according to requirements, lack of phase, stator and rotor friction Remove foreign objects, replace impeller, replace motor matching user voltage and frequency, replace fuse and faulty motor components
3 Current too high Bearings worn, impeller and duct friction, impeller blocked, lack of phase, other obstruction Replace bearings, adjust the gap between impeller and ducting,  repair circuits, defrosting
4 excessive noise or vibration Impeller damaged, loose stand, grill damaged, airflow obstruction Replacement of impeller, tighten loose parts. Repair and replace grill, defrost.  
5 Leakage, low insulation resistance Motor storage influent. Moisture Dry motor before use.
 
Technical parameter:
Dry cooler D2 series parameter(fin space 2.1mm)
Type D2-148-4x630 D2-166-4x630 D2-175-4x630 D2-228-6x630 D2-250-6x630 D2-276-6x630 D2-310-8x630 D2-343-8x630 D2-364-8x630 D2-392-10x630
Capacity Water KW 147.99 165.85 175.21 227.85 250.42 276.53 309.85 342.73 364.07 391.99
20% Et. Glycol KW 142.42 161.57 170.91 219.09 244.69 270.22 301.18 333.55 354.64 383.3
Air flow M3/h 76459 74341 72134 114686 111511 108188 152911 148675 144255 191136
Fan No. X φ 2x2x630 2x2x630 2x2x630 2x3x630 2x3x630 2x3x630 2x4x630 2x4x630 2x4x630 2x5x630
Fan motor
400/3N/50HZ
A 20.4 20.4 20.4 30.6 30.6 30.6 40.8 40.8 40.8 51.00
Sound pressure level dB(A)10m 64 64 64 66 66 66 67 67 67 68
Dimension L mm 2186 2186 2186 3250 3250 3250 4250 4250 4250 5250
H mm 1874 1874 1874 1874 1874 1874 1874 1874 1874 1874
D mm 2100 2100 2100 2100 2100 2100 2100 2100 2100 2100
D1 mm 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000
L1 mm 963 963 963 963 963 963 963 963 963 963
L2 mm 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
L3 mm 1963 1963 1963 2963 2963 2963 3963 3963 3963 4963
Connections inlet φ mm 2XDN50 2XDN65 2XDN65 2XDN65 2XDN80 2XDN80 2XDN80 2XDN80 2XDN100 2XDN100
Connections onlet φ mm 2XDN50 2XDN65 2XDN65 2XDN65 2XDN80 2XDN80 2XDN80 2XDN80 2XDN100 2XDN100
Product
weight(empty)
kg 769 811 853 1134 1197 1261 1498 1589 1673 1864
 
Glycol-Water Coolers for Heating Plants and Power Plants
Glycol-Water Coolers for Heating Plants and Power Plants


 
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Diamond Member Since 2010

Suppliers with verified business licenses

Manufacturer/Factory
Management System Certification
ISO 9001
OEM/ODM Availability
Yes