Venttk First-Class Ahu for Clean Room Hydronic Air Handling Unit
Contact Supplier
Product Highlights
- Customizable Dimensions: Size, Weight, and Cooling Capacity are fully customized to meet specific project requirements.
- High Energy Efficiency: Features high-efficiency centrifugal fans and optional heat recovery devices with efficiency over 75%.
- Versatile Application: Suitable for clean rooms, hospitals, offices, and industrial settings with various structural options.
- Advanced Filtration: Standard G4 filters with options for F8, nanocrystalline carbon, and other high-efficiency filters.
- Low Noise Operation: Ultra-low noise level achieved through sound deadening sections and efficient fan design.
- Flexible Configuration: Modular design allows for mixing, cooling, heating, humidifying, and fan sections to be combined.
- Durable Construction: Galvanized sheet material with higher corrosion durability for long-lasting performance.
- Reliable Support: 1-year warranty with online technical support available for troubleshooting and assistance.
Product Attributes
- Customization
- Available
- After-sales Service
- Online Support
- Warranty
- 1 Year
- Model NO.
- VT6721
- Type
- Air Handling Unit
- Air Tube Material
- Galvanized Sheet
- Corrosion Durability
- Higher
- Operating Voltage
- 380/400 VAC
- Noise Level
- Ultra Low
- Application Fields
- Medicine
- Mounting
- Floor Standing
- Lifetime
- 10~15 years
- Certification
- ISO
- Condition
- New
- OEM Customized
- Supported
- Item
- Air Handing Unit
- Cooling Capacity
- Customized
- Weight
- Customized
- Size
- Customized
- Power
- 3n-380V-50Hz
- Blower
- High Efficient Centrifugal Fan
- Chilled Water Coil (Option)
- High Efficient Copper Tube Aluminum Fin
- Humidifier
- Electrode Type/ Steam/ Electrothermic Type
- Air Filter
- Primacy Filter G4
- Compressor a
- Hermetic Scroll (Fixed Frequency System)
- Refrigerant
- R22/R407c/R410A
- Margin Blast Pressure
- 300PA
- Water Flow (M³/H)
- 2.6
- Refrigerant Mode
- Thermal Expansion Valve/ Electronic Expansion Valv
- Transport Package
- Film Packing
- Specification
- customized
- Trademark
- Venttk
- Origin
- Shanghai, China
- HS Code
- 8419500090
- Production Capacity
- 300 Sets/Month
Product Images of Venttk First-Class Ahu for Clean Room Hydronic Air Handling Unit
Find Similar Products
Product Description
Air cooled direct expansion type air handling unit
| unit characteristics | Model: GT-ZKW-()DX | 20 | 30 | 40 | 50 | 65 | 80 | 100 | |
| Cooling capacity | KW | 10.1 | 15.3 | 20.3 | 25.5 | 32.3 | 38.6 | 52.0 | |
| Heating capacity | KW | 10.3 | 15.7 | 20.8 | 26.1 | 33.5 | 39.5 | 53.2 | |
| Supply air volume | M³/h | 2000 | 3000 | 4000 | 5000 | 6500 | 8000 | 10000 | |
| Margin blast pressure | Pa | 200 | 250 | 300 | 300 | 400 | 400 | 500 | |
| Power | 3N-380V-50Hz | ||||||||
| Indoor unit |
Blower | Type | High efficient centrifugal fan | ||||||
| KW | 0.55 | 0.75 | 1.5 | 2.2 | 3.0 | 3.0 | 5.5 | ||
| Chilled water coil (option) |
Type | High efficient copper tube aluminum fin | |||||||
| Water flow (m³/h) |
1.7 | 2.6 | 3.5 | 4.4 | 5.6 | 6.6 | 8.9 | ||
| Segment length (mm) |
300 | 300 | 300 | 300 | 300 | 300 | 300 | ||
| Heater | Type | Stainless steel tubular electric heater/ Steam heat coil/ Hot water heat coil | |||||||
| KW | 6 | 9 | 12 | 18 | 24 | 24 | 30 | ||
| segment length (mm) |
300 | 300 | 300 | 300 | 400 | 400 | 400 | ||
| Humidifier | Type | Electrode type/ Steam/ Electrothermic type/ Wet film | |||||||
| KW | 3 | 4 | 5 | 8 | 8 | 12 | 12 | ||
| segment length (mm) |
400 | 400 | 400 | 400 | 400 | 400 | 400 | ||
| Air filter | Type | Primary filter G4( Middle filter F8 &Nanocrystalline carbon filter) | |||||||
| Noise | dB(A) | 60 | 60 | 61 | 62 | 63 | 63 | 65 | |
| Size | L (mm) | 1800 | 2000 | 2000 | 2100 | 2100 | 2200 | 2400 | |
| W (mm) | 730 | 1030 | 1030 | 1030 | 1140 | 1340 | 1340 | ||
| H (mm) | 788 | 788 | 1115 | 1115 | 1115 | 1115 | 1420 | ||
| Weight | KG | 140 | 180 | 320 | 400 | 580 | 660 | 800 | |
| Outdoor unit | Model: GT-WL- | 10 | 15 | 20 | 25 | 35 | 40 | 55 | |
| Compressor A | Type | Hermetic Scroll ( Fixed frequency system) | |||||||
| Quantity | 1 | 1 | 1 | 1 | 1 | 2 | 2 | ||
| Input power A | KW | 3.4 | 4.8 | 6.3 | 8.0 | 9.8 | 12.7 | 16.1 | |
| Compressor B | Type | Hermetic Scroll( Frequency conversion system) | |||||||
| Quantity | 1 | 1 | 1 | 1 | 1 | 2 | 2 | ||
| Input power B | KW | 3.3 | 4.6 | 6.2 | 7.7 | 9.7 | 12.6 | 15.6 | |
| Refrigerant | Type | R22/R407C/R410A | |||||||
| Mode | Thermal expansion valve/ Electronic expansion valve | ||||||||
| Noise | dB(A) | 63 | 63 | 64 | 64 | 65 | 65 | 76 | |
| Size | L (mm) | 850 | 850 | 980 | 980 | 980 | 1880 | 1880 | |
| W (mm) | 850 | 850 | 980 | 980 | 980 | 980 | 980 | ||
| H (mm) | 1080 | 1080 | 1080 | 1080 | 1234 | 1080 | 1080 | ||
| Weight | KG | 130 | 135 | 150 | 180 | 220 | 280 | 320 | |
| Connection Pipe diameter | liquid pipe(mm) | 12.7 (9.52) |
12.7 (9.52) |
12.7 (12.7) |
15.88 (12.7) |
15.88 (12.7) |
15.88*2 (12.7*2) |
15.88*2 (12.7*2) |
|
| gas pipe(mm) | 15.88 (12.7) |
19.05 (15.88) |
19.05 (15.88) |
28.6 (22.23) |
15.88 (12.7) |
22.23*2 (19.05*2) |
28.6*2 (22.23*2) |
||
Note:
Cooling condition: indoor dry bulb/wet bulb 27/19 ºC;Outdoor dry bulb/wet bulb 35/24 ºC;
Heating condition: indoor dry bulb/wet bulb 20/- ºC;Outdoor dry bulb/wet bulb 7/6 ºC;
Air volume, pressure, power in the table is standard parameters. It can be separately designed according to customer's requirements;
Chilled water coil as optional parts, according to the customer site requirements configured to double cold source unit;
Heater, humidifier, heat recovery device as optional parts, according to the customer requirements configured to the specific form
Unit standard USES G4 level filters, according to the customer requirements configured to the other forms;
Unit length does not include the function section. Such as heating section humidification secition. Specific details please consult us;
Air cooled split type air conditioning unit without refrigerant leaving the factory, refrigerant models need to indicated in the order;
Noise data is measured 2 m in the front of the unit , 1.2 m high, when cooling under the standard air volume;
Inside of bracket is R410A refrigerant type connection pipe diameter, the connection copper pipe between the indoor and outdoor unit should within 35 meters.
Chilled water type air handling unit
| Model GT-ZKW- | 20 | 40 | 60 | 80 | 100 | 150 | 200 | 250 | 300 | ||
| Air volume(m³/h) | 2000 | 4000 | 6000 | 8000 | 10000 | 15000 | 20000 | 25000 | 30000 | ||
| Outlet air pressure(pa) | 300 | 300 | 400 | 500 | 500 | 600 | 750 | 750 | 750 | ||
| Supply fan capacity(kw) | 1.1 | 1.5 | 2.2 | 4 | 5.5 | 11 | 15 | 15 | 18.5 | ||
| Cooling | 4 Rows | Return air(kw) | 12.2 | 23.9 | 35.9 | 48 | 60 | 90 | 120 | 150 | 179 |
| water flow(m³/h) | 2.2 | 4.2 | 6.1 | 8.2 | 10.5 | 15.3 | 20.4 | 23.8 | 28.2 | ||
| all fresh air(kw) | 22 | 43.8 | 62 | 90 | 112 | 156 | 210 | 265 | 310 | ||
| water flow(m³/h) | 3.8 | 7.7 | 11 | 15.5 | 19.2 | 27.3 | 36.5 | 45.8 | 55 | ||
| pipe diameter (DN) | 25 | 32 | 40 | 40 | 40 | 50 | 65 | 65 | 80 | ||
| 6 Rows | Return air(kw) | 17 | 30.1 | 45.2 | 60 | 75 | 113 | 151 | 188 | 210 | |
| water flow(m³/h) | 2.8 | 5.3 | 7.7 | 10.5 | 13.6 | 19.2 | 25.5 | 30.2 | 36 | ||
| all fresh air(kw) | 30.5 | 58 | 88 | 118 | 150 | 200 | 288 | 355 | 420 | ||
| water flow(m³/h) | 5.1 | 10 | 15.2 | 20.2 | 26.2 | 35.5 | 49 | 70 | 72.5 | ||
| pipe diameter (DN) | 32 | 32 | 40 | 40 | 50 | 65 | 65 | 80 | 80 | ||
| 8 Rows | Return air(kw) | 18.3 | 35.2 | 53 | 70 | 90 | 132 | 176 | 220 | 264 | |
| water flow(m³/h) | 3.2 | 6.2 | 8.9 | 12.2 | 16.2 | 22.2 | 30.2 | 37.2 | 44.2 | ||
| all fresh air(kw) | 34.8 | 70 | 101 | 138 | 178 | 245 | 332 | 410 | 500 | ||
| water flow(m³/h) | 5.8 | 12 | 17.5 | 23.5 | 30.8 | 42.5 | 57.1 | 71 | 85 | ||
| pipe diameter (DN) | 32 | 32 | 40 | 40 | 50 | 65 | 65 | 80 | 80 | ||
| Heating | 2 Rows | Return air(kw) | 20 | 42 | 60 | 84 | 108 | 150 | 200 | 250 | 300 |
| water flow(m³/h) | 0.8 | 1.9 | 2.6 | 3.7 | 4.6 | 6.5 | 8.7 | 11 | 13 | ||
| all fresh air(kw) | 18 | 38 | 54 | 70 | 100 | 125 | 180 | 210 | 280 | ||
| water flow(m³/h) | 0.8 | 1.7 | 2.4 | 3.2 | 4.5 | 5.5 | 7.8 | 10 | 12 | ||
| pipe diameter (DN) | 25 | 32 | 40 | 40 | 40 | 40 | 50 | 50 | 65 | ||
| 4 Rows | Return air(kw) | 28 | 56 | 80 | 110 | 140 | 200 | 250 | 320 | 380 | |
| water flow(m³/h) | 1.2 | 2.4 | 3.5 | 4.8 | 6.3 | 9 | 11 | 13.5 | 18.2 | ||
| all fresh air(kw) | 32 | 62 | 90 | 125 | 150 | 220 | 300 | 380 | 450 | ||
| water flow(m³/h) | 1.5 | 2.7 | 3.8 | 5.4 | 6.8 | 9.5 | 13.5 | 16.2 | 19.5 | ||
| pipe diameter (DN) | 32 | 32 | 40 | 40 | 40 | 50 | 50 | 65 | 65 | ||
| Function section outside dimension |
Mixing section | Length(mm) | 500 | 500 | 500 | 550 | 600 | 800 | 800 | 800 | 800 |
| Width(mm) | 950 | 950 | 1080 | 1250 | 1600 | 1600 | 2000 | 2200 | 2200 | ||
| Height(mm) | 980 | 980 | 1080 | 1250 | 1320 | 1470 | 1680 | 1880 | 2200 | ||
| Pre-filter section | Length(mm) | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | |
| Width(mm) | 950 | 950 | 1080 | 1250 | 1600 | 1600 | 2000 | 2200 | 2200 | ||
| Height(mm) | 980 | 980 | 1080 | 1250 | 1320 | 1470 | 1680 | 1880 | 2200 | ||
| Medium efficiency filter section | Length(mm) | 500 | 500 | 500 | 500 | 500 | 500 | 500 | 500 | 500 | |
| Width(mm) | 950 | 950 | 1080 | 1250 | 1600 | 1600 | 2000 | 2200 | 2200 | ||
| Height(mm) | 980 | 980 | 1080 | 1250 | 1320 | 1470 | 1680 | 1880 | 2200 | ||
| Cooling coil section | Length(mm) | 600 | 600 | 700 | 700 | 700 | 800 | 800 | 1000 | 1000 | |
| Width(mm) | 950 | 950 | 1080 | 1250 | 1600 | 1600 | 2000 | 2200 | 2200 | ||
| Height(mm) | 980 | 980 | 1080 | 1250 | 1320 | 1470 | 1680 | 1880 | 2200 | ||
| Heating section | Length(mm) | 300 | 300 | 300 | 400 | 400 | 400 | 400 | 400 | 400 | |
| Width(mm) | 950 | 950 | 1080 | 1250 | 1600 | 1600 | 2000 | 2200 | 2200 | ||
| Height(mm) | 980 | 980 | 1080 | 1250 | 1320 | 1470 | 1680 | 1880 | 2200 | ||
| Humidifying section | Length(mm) | 400 | 400 | 400 | 400 | 400 | 400 | 400 | 400 | 400 | |
| Width(mm) | 950 | 950 | 1080 | 1250 | 1600 | 1600 | 2000 | 2200 | 2200 | ||
| Height(mm) | 980 | 980 | 1080 | 1250 | 1320 | 1470 | 1680 | 1880 | 2200 | ||
| Fan section | Length(mm) | 500 | 500 | 900 | 400 | 1100 | 1400 | 1600 | 1700 | 1850 | |
| Width(mm) | 950 | 950 | 1080 | 1250 | 1600 | 1600 | 2000 | 2200 | 2200 | ||
| Height(mm) | 980 | 980 | 1080 | 1250 | 1320 | 1470 | 1680 | 1880 | 2200 | ||
| Current balance section | Length(mm) | 400 | 400 | 500 | 900 | 500 | 600 | 600 | 600 | 700 | |
| Width(mm) | 950 | 950 | 1080 | 1250 | 1600 | 1600 | 2000 | 2200 | 2200 | ||
| Height(mm) | 980 | 980 | 1080 | 1250 | 1320 | 1470 | 1680 | 1880 | 2200 | ||
| Sound deadening section | Length(mm) | 800 | 800 | 800 | 500 | 800 | 1000 | 1000 | 1000 | 100 | |
| Width(mm) | 950 | 950 | 1080 | 1250 | 1600 | 1600 | 2000 | 2200 | 2200 | ||
| Height(mm) | 980 | 980 | 1080 | 1250 | 1320 | 1470 | 1680 | 1880 | 2200 | ||
| Air outlet section | Length(mm) | 400 | 400 | 400 | 800 | 500 | 600 | 600 | 800 | 800 | |
| Width(mm) | 950 | 950 | 1080 | 1250 | 1600 | 1600 | 2000 | 2200 | 2200 | ||
| Height(mm) | 980 | 980 | 1080 | 1250 | 1320 | 1470 | 1680 | 1880 | 2200 | ||
Note:
Cooling condition: supply water/return water 7/12 ºC, indoor dry bulb/wet bulb 27/19ºC , fresh air dry bulb/wet bulb 35/28ºC ;
Heating condition: supply water/return water 60/50ºC, indoor dry bulb/wet bulb 20/-ºC,outdoor air dry bulb/wet bulb 7/6ºC;
Air volume, pressure, power in the table is standard parameters. It can be separately designed according to customer's requirements;
Heater, humidifier, heat recovery device as optional parts, according to the customer requirements configured to the specific form;
Unit standard USES G4 level filters, according to the customer requirements configured to the other forms;
Unit length is decided for the number of function section. Specific details please consult us;
Application
The units are widely used in the air system of many inductries like mechanical ,electronic, textile,medical,chemical,energy and foo inductries ,etc. the units are also ideal solution for restaurants, office buildings,hospitals,theaters,supermarkets and palaestra.
Air handling unit drawing
General comfortable occasion air handling unit
Configuration of basic function, early efficient filter and hot coil in air handling units (choose wet membrane humidification), it has the simple and highly controllable size characteristics of the function.
Suitable for general building room comfort air conditioning process.
Air handling units for all fresh air occasion
Configuration of basic function, primary filter or medium efficiency air filter, cooling coil ( enough margin, meet the needs of extreme conditions), it use steam, hot water heating, or natural gas direct combustion heating section
( high thermal efficiency, low running cost); it also need to set the reheat, can choose the cooling reheat to control humidity and enhance the energy level, or set up the electric heater, to realize thermal compensation again after the summer dehumidification. It mainly meet the aerospace, automotive, instruments and meters, precision machining and other special industry requirements for air quality.
Air handling units for general technology purification occasion
The configuration of the function section are: mixed section, cooling section, fan section, primary efficiency filter (G4) section, medium efficiency filter (F8) section. At the same time,it equipped with electric heating, electric humidification, muffler to satisfy high cleanliness, constant temperature and humidity,low noise control cleanliness project. Such as: inspection and quarantine laboratory, electronics factory workshop, biological engineering R&D center, food processing, precision machinery, pharmaceutical processing and storage area and other places which have strict requirements for temperature and humidity, cleanliness.
Air handling units for general technology purification occasion
In addition to the general horizontal units, we can provide several kinds of structure forms of units, such as: vertical, ceiling, roof waterproof, etc.. They can meet the demand of different occasions. Ceiling structure unit can be installed on the ceiling. It is suitable for narrow room air conditioning or the area which has not a special equipment room;Roof waterproof structure unit can be installed on the outdoor roof or outdoor floor. Setting rofessional rainproof device and panel special thermal insulation design unit.
Air handling units for operating room and high clean requirement occasion
In addition to the basic function of configuration, with primary efficiency filter or medium efficiency filter, it equipped with electric heating and humidification section. Considering particularity of medical situations, AHU adopt double cold source system ( chilled water + direct expansion) and efficient unhoused centrifugal fan, provide frequency conversion control, in order to satisfy the high reliability requirements.
Air handling units with heat recovery device
Can configured with wheel heat recovery device, hot and cold air passes through hot wheel, heat and moisture exchange is carried out by the difference of temperature and steam pressure between fresh air and exhaust air, effective recovery of sensible heat and latent heat in exhaust air, achieve the purpose of energy conservation.Honeycomb structure with aluminum foil carrier and high efficient moisture absorbing coating for heat storage core body of heat exchanger, excellent characteristics of heat storage, moisture absorption and heat transfer, efficiency is higher than 75%.
Can configured with plate fin heat recovery device, so that the cold hot air flow directly through the same heat exchanger, in order to achieve the purpose of heat exchange.The heat exchanger adopts ginning aluminum foil, corrugated aluminum foil heat exchanger made of heat conductor, no interme-diate heat medium is required,no power consumption,no loss of temperature difference,temperature efficiency is higher than 75%.
About the Supplier
This supplier has been audited by SGS. Verify the report on the official SGS website with ID "QIP-ASR2241984". Items marked "" are certified.
Company Profile
We VENTTK:
Best quality and best price is what we pursued. Customer`s meet is what we cared.
Our products have been exported to Europe, North of America, Middle East, South of Africa and southeast Asia.
We sincerely welcome customers all over the world to visit our company and set up business relationship for mutual benefit.
We have our own laboratories, professional equipment.
A variety of performance testing of product can be finished by ourselves.
We have complete quality testing system.
5 more years experienced team strictly control production process.
Our condensers and evaporators can be widely used in air conditioners, heat pumps, fan coils, air handing units, welding machines and other area. We can only only manufacture copper pipe condensers and evaporators, but also manufacture stainless steel pipe and aluminum pipe condensers and evaporators.
Our rooftop air conditioners are easy to be installed and maintained. As they are installed on the top roof, so they will not spare the room space. They are weather proof and have high efficiency.
Our precision air conditioner can control temperature in +-1C and humidity in +-5%. It can be used in data center and telecom base station. Most parts are world famous brand.
We ensure brand quality and good reputation. Our company can provide high quality service, consistent service warm for the majority of customers.
About Our Factory & Business Background
- Address
- Room 1801, Building 1, Lane 1100, Lanzhou Road, Yangpu District, Shanghai, China
- Terms of Payment
- LC, T/T, PayPal, Western Union
- International Commercial Terms(Incoterms)
- FOB, CFR, CIF, DAT, EXW, Others
- Average Lead Time
-
Peak Season Lead Time: 1-3 months
Off Season Lead Time: one month - Nearest Port
- SHANGHAI, GUANGZHOU, QINGDAO
Our Production Capability & Technical Expertise
Our Industry Experience & Global Business Record
- Export Year
- 2009-01-01
- Main Markets
- North America, South America, Eastern Europe, Southeast Asia, Africa, Oceania, Mid East, Eastern Asia, Western Europe
FAQ
- What customization options are available?
- We support OEM customization for Size, Weight, Cooling Capacity, and Power. Specific configurations can be designed according to customer requirements.
- What is the warranty period?
- The product comes with a 1-year warranty and includes online support for after-sales service.
- What are the typical applications for this AHU?
- It is widely used in mechanical, electronic, textile, medical, chemical, and energy industries, as well as for hospitals, offices, and clean rooms.
- What filtration levels are standard or optional?
- The unit standardly uses G4 level filters. Options include F8 medium efficiency filters, nanocrystalline carbon filters, and others based on requirements.
- What is the lead time for production?
- The average lead time is one month during the off-season and 1-3 months during the peak season.
- What payment terms are accepted?
- We accept LC, T/T, PayPal, and Western Union as terms of payment.
- Can the unit be installed on the roof or ceiling?
- Yes, we provide vertical, ceiling, and roof waterproof structure forms to suit different installation environments.
- What is the noise level of the unit?
- The unit features ultra-low noise levels, measured 2 meters in front of the unit, ranging from 60 to 76 dB(A) depending on the model.
Send your message to this supplier
People who viewed this also viewed
-
US$240.00 / Piece
-
US$240.00 / Piece
-
US$1,888.00-2,000.00 / Piece
-
US$1,500.00-2,000.00 / Piece
-
US$14,000.00-16,000.00 / Piece
-
US$2,500.00 / Piece
-
US$1,520.00 / Piece
-
US$580.00 / Piece
-
US$18,900.00-21,000.00 / Piece
Find Similar Products By Category
- Supplier Homepage
- Products
- Air conditioner
- Air handling unit
- Venttk First-Class Ahu for Clean Room Hydronic Air Handling Unit
Related Categories
Hot Searches
- Power Unit Factories
- Electronic Unit Factories
- Water Unit Factories
- Air Cooled
- New Ahu
- Industrial Ahu
- Hvac Ahu
- Ahu Unit
- Ahu Air Conditioner
- Water Cooled Ahu Bulkbuy