Basic Info.

Model NO.
WRF88ZA
Corrosion Durability
Higher
Operating Voltage
380/400 VAC
Noise Level
Low
Application Fields
Mechanical Engineering
Mounting
Floor Standing
Lifetime
>20 years
Certification
RoHS, ISO
Condition
New
Product
Air Conditioner
Cooling Capacity
72kw
Heating Capacity
37.1kw
Supply Air
5800
Power
3n-380V-50Hz
Compressor
Efficient Scroll Closed
Evaporator
Tube Fin Heat Exchanger
Condenser
Tube Fin Heat Exchanger
Refrigerant
R22/R407c
Air Filter
Initially Effect Plate Filter
Transport Package
Export Packaging
Specification
850kg
Trademark
VENTTECH
Origin
Shanghai, China(Mainland)
HS Code
8415830000
Production Capacity
1500units Per Month

Product Description

packaged heat pump type rooftop air conditioner Description:

1. Air cooled rooftop air conditioner.
2. Cooling capacity: 8kw to 90kw, a variety of choices.
3. High external pressure.
4. Applicable to residential and commercial buildings, hotels, and scientific research units, factories and enterprises and so on.

packaged heat pump type rooftop air conditioner Features:
1. It is packaged air conditioner which integrates condensing part, evaporating part & control part into a whole unit, firstly promoted & applied in South America, North Europe & Australia.

2. It is air cooled direct evaporation & expansion air conditioner, has no need on cooling water & chilled water system, dispenses with cooling tower/cooling water pump/chilled water pump,  relative pipe work, electric control & terminal equipments, saves user investment.

3. It integrates evaporating part & condensing part into a whole unit which is installed outside to save indoor space, user will only need to install the duct, no need to connect refrigerant pipe work, it works under intellectual control without special care.

 
Application range:
It is mainly applied to factories, schools, auditoriums, warehouses, etc.

Structure:
1. Panels and frame are made from galvanized steel protected with polyester powder painting to ensure total resistance to atmospheric agents.
2. Direct expansion coils with condensate drain tray.

Hermetic compressor
1. High efficiency scroll compressor for the whole range, with built-in thermal overload cut-out and crankcase heater, mounted on rubber vibration dampers.
2. Ripple type acoustic insulation for compressor section, and thermal insulation for coil and fan section, low noise.

Centrifugal fan
1. Forward curve centrifugal fans for air treatment section and axial fans for condensation section.
2. Front, side and underside air discharge of the treatment unit.
3. High external pressure, long air supply distance.

Electric panel
1. Electric panel consists of breakers and contactors for compressors and fan motors, phase sequence relay and other necessary protection devices for the main components
2. Easy operation line controller
3. Cooling/Heating/Auto
3. Error indication
4. Timing on/off

Optional
1. Economizer with fresh, return air dampers and fresh air hood
2. Free cooling function for low ambient temperature
3. Low ambient control device for operation of outdoor units at ambient temperatures from less than 20C down to -10C
4. BMS devices
4. T3 (Tropical climate)
5. Condenser coil guard
6. Roof curb
7. Metal / aluminum filter
8. Air pressure switch for indoor fan
9. High static condenser fan option with sealed + drain condensing section
10. Optional water heating coil
11. Metal or plastic mesh on condenser coil
12. Optional supply / return air configurations
13. Upgraded evaporator fan motor drives
14. G4 filter, plate and bag filter

 
Rooftop AIr Conditioner Model WRF12ZA WRF 15ZA WRF18ZA WRF24ZA WRF30ZA WRF 35ZA
WF12ZA WF 15ZA WF18ZA WF24ZA WF30ZA WF 35ZA
Cooling capacity kW 12 15.2 17.5 24 30.3 35.6
Heating capacity kW 13.2 16.6 18.4 26.5 33.3 37.7
Energy regulation
 
% 0,100% 0,50,100%
Power 380V / 3Ph / 50HZA
Cooling input capacity kW 4.1 5.3 5.5 8.8 11.3 12.3
Heating input capacity kW 3.8 4.8 5.1 8.2 10.4 11.3
Start current A 48 62 63 63 74 76
Cooling running current A 7.4 9.7 10.2 16.1 21.2 23.3
Heating running current A 6.9 9.2 9.7 15.1 20.1 22.2
Throttling method
 
Thermal expansion valve
 
Cooling system 1 1 1 1 2 2
Refrigerant R410A
Compressor Compressor type Hermetic scroll compressor
 
Qty 1 1 1 1 2 2
Condensation side
 
 
Condenser Type Copper tube and aluminum fin
Qty 1 1 1 1 1 1
Drive type Direct drive
Motor power kW 0.25 0.37 0.37 0.55 0.75 0.75
Air volume m3 /h  4600 7800 7800 9000 12600 12600
Evaporation side
 
 
Evapotator Type Copper tube and aluminum fin
Qty 1 1 1 1 1 1
Motor power kW 0.32 0.37 0.45 1.1 1.5 2.2
Air volume m3 /h 2100 2600 3400 4100 5200 6300
Drive type Direct drive Pulley
Static pressure(Pa) 100 100 100 200 200 250
Filter Aluminum filter G3
Noise dB(A) 67 67 68 71 72 72
Refrigerant filling volume(kg) 3.1 3.1 4.3 2x3.1 2x3.1 2x4.3
External dimension L mm 1410 1410 1410 1978 1978 1978
W mm 1100 1100 1100 1175 1175 1175
H mm 1095 1095 1095 1095 1095 1095
Weight kg 240 260 290 420 480 500
Model WRF45ZA WRF50ZA WRF 60ZA WRF72ZA WRF 90ZA WRF105ZA
WF 45ZA WF 50ZA WF 60ZA WF 72ZA WF90ZA WF 105ZA
Cooling capacity kW 44.5 50 60 70 90 105
Heating capacity kW 48.7 54.3 64 75.4 96.2 113.2
Energy regulation % 0,33,66,100 0,30,70,100 0,50,100 0,50,100 0,33,66,100 0,33,66,100
Power   380V / 3Ph / 50HZA
Cooling input capacity kW 17 19.5 22.8 26.7 32.9 39.7
Heating input capacity kW 15.6 18 21 24.8 30.4 36.7
Start current A 168 186 175 199 197 266
Cooling running current A 31.7 35.6 39.9 48.3 61 70.6
Heating running current A 29.9 33.5 37.5 45.4 57.3 66.3
Throttling method
 
                                   Thermal expansion valve
 
Cooling system 1  
Refrigerant R410A
Compressor Compressor type Hermetic scroll compressor   
Qty 2 2 2 2 3 3
Condensation side
 
Condenser Type Copper pipe copper fin
Fan Qty 1 1 1 1 2 2
Drive type Direct drive
Motor power kW 1.1 1.5 1.5 2.2 2X1.1 2X1.5
Air volume m3 /h 16500 21000 21000 27000 33000 42000
      a 2.65 3.82 3.82 5.49 2.65 3.82
      kw 1.14 2.02 2.02 2.875 1.14 2.02
Evaporation side
Evaporator Type Evaporator
  Qty   1 1 1 1 1
Motor power   3 3 4 4 5.5 5.5
Air volume   7600 8500 10900 12500 16000 19500
Drive type  
Static pressure(Pa) 250 250 300 300 300 300
Filter Aluminum filter G3
Noise dB(A) 73 73 73 75 74 75
Refrigerant filling volume(kg) 4.3+ 4.3+8.5 2x7.5 2x8.5 3x7.5 3x8.5
External dimension L mm 2268 2268 2298 2298 2878 2878
W mm 1440 1440 1650 1650 2140 2140
H mm 1167 1167 1400 1400 1964 1964
Weight   750 770 880 960 1160 1350