Customization: | Available |
---|---|
Type: | Window Mounted Air Conditioners |
Capacity: | 27000-48000 BTU |
Still deciding? Get samples of US$ 568/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
We are a leading and professional air handing unit, rooftop and precision air conditioner factory which has more than 16 years experience in china. Now we have two factories. One is mainly manufacturing condensers and evaporators, the other one is mainly manufacturing central air conditioners like roof-top air conditioners, precision air conditioners and air handing units. Both of our factories are ISO certificated.
Shanghai Venttk provides customers with high-quality and high-effect products based on advanced production technologies ,mature manufacturing processes and strict quality controls and keep communicating with understanding customers demands,which repays us with self improvements and the trust and recognition of customers.
We are 'Detail Oriented, Focus on Quality, Never Cut Corners'.
Product Description
Specification:
GT-HFM series constant temperature and humidity precision air conditioner specification 1 | |||||||||||
Model GT-HFM-() | 07 | 12 | 15 | 18 | 20 | 24 | 27 | 30 | |||
Specifi cation |
Total cooling capacity | kW | 7.5 | 12.6 | 15.3 | 18.6 | 21.8 | 24.2 | 27.5 | 31.8 | |
Sensible cooling capacity | kW | 6.9 | 11.7 | 14.1 | 17.4 | 20.2 | 22.4 | 25 | 29.5 | ||
Electric heating | kW | 3 | 6 | 6 | 9 | 9 | 9 | 12 | 15 | ||
Air volume 2* | m3/h | 1800 | 3250 | 4100 | 5200 | 5400 | 6600 | 7500 | 9000 | ||
Outlet air pressure 2* | Pa | 25 | 25 | 25 | 50 | 50 | 75 | 75 | 75 | ||
Noise 3* | dB(A) | 54 | 54 | 55 | 56 | 56 | 56 | 56 | 56 | ||
Temperature control range and accuracy |
ºC | 18~28,±1 | |||||||||
Humidity control range and accuracy |
% | 45~70,±5 | |||||||||
Power | 3N-380V-50Hz | ||||||||||
Input power 4* | kW | 6 | 11 | 12.6 | 16.8 | 17.5 | 19 | 23.9 | 28.9 | ||
Indorr unit |
Supply air fan | type | low noise centrifugal type | ||||||||
capacity | kW | 0.32 | 0.55 | 0.75 | 1.1 | 1.1 | 1.5 | 2.2 | 2.2 | ||
Electrode humidifier |
humidification volume |
kg/h | 3 | 3 | 5 | 5 | 5 | 8 | 8 | 8 | |
Electric heating |
capacity | kW | 3 | 6 | 6 | 9 | 9 | 9 | 12 | 15 | |
Evaporator type | Inner grooved copper tube and aluminum fin | ||||||||||
Air filter | primary efffect plate type filter | ||||||||||
Dimension | L | mm | 950 | 1200 | 1200 | 1200 | 1200 | 1600 | 1600 | 1600 | |
W | mm | 580 | 680 | 680 | 680 | 680 | 780 | 780 | 780 | ||
H | mm | 1800 | 1880 | 1880 | 1880 | 1880 | 2000 | 2000 | 2200 | ||
Weight | kg | 190 | 230 | 270 | 290 | 300 | 400 | 430 | 510 | ||
Outdoor unit |
Model GT-( )*quantity | WL08 *1 |
WL12 *1 |
WL15 *1 |
WL18 *1 |
WL20 *1 |
WL25 *1 |
WL27 *1 |
WL30 *1 |
||
compressor | type | Totally enclosed scroll type | |||||||||
quantity | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |||
condenser type |
Inner grooved copper tube and aluminum fin | ||||||||||
Condensing fan |
type | Low noise axial type | |||||||||
capacity | kW | 0.37 | 0.37 | 0.37 | 0.55 | 0.55 | 0.55 | 0.75 | 0.75 | ||
Dimension | L | mm | 800 | 850 | 850 | 980 | 980 | 980 | 980 | 980 | |
W | mm | 800 | 850 | 850 | 980 | 980 | 980 | 980 | 980 | ||
H | mm | 980 | 1080 | 1080 | 1080 | 1080 | 1080 | 1234 | 1234 | ||
Weight | kg | 90 | 120 | 150 | 170 | 170 | 205 | 210 | 220 | ||
Freon 5* | type | R22(R407C/R410A) | |||||||||
control method | Out balance expansion valve | ||||||||||
Collecting pipe 6* | liquid pipe`s diameter |
mm | 9.52 9.52 |
12.7 9.52 |
12.7 9.52 |
15.88 12.7 |
15.88 12.7 |
15.88 12.7 |
15.88 12.7 |
15.88 12.7 |
|
gas pipe`s diameter |
mm | 15.88 12.7 |
19.05 15.88 |
19.05 15.88 |
22.23 19.05 |
22.23 19.05 |
28.6 22.23 |
28.6 22.23 |
28.6 22.23 |
||
1.Cooling condition: Indoor dry bulb/wet bulb: 24/17ºC;Outdoor dry bulb/wet bulb: 35/24ºC; | |||||||||||
2.Air volume\static pressure are standard data, it can be designed by client | |||||||||||
3.Noise data is measured 3 meters far away from the units | |||||||||||
4.The input power means the power consumption under max condtion | |||||||||||
5.If freon is R410A or R407C, please noted it in the order |