  • Model NO.: GT-ZKW-200
  • Air Tube Material: Galvanized Sheet
  • Operating Voltage: 380/400 VAC
  • Application Fields: Mechanical Engineering
  • Lifetime: >20 years
  • Condition: New
  • Cooling Capacity: 40kw
  • Supply Air: 5800
  • Compressor: Efficient Scroll Closed
  • Condenser: Tube Fin Heat Exchanger
  • Air Filter: Initially Effect Plate Filter
  • Specification: customized
  • HS Code: 8415830000
  • Type: Air Handling Unit
  • Corrosion Durability: Higher
  • Noise Level: Low
  • Mounting: Floor Standing
  • Certification: RoHS, ISO
  • Product: Air Conditioner
  • Heating Capacity: 37.1kw
  • Power: 3n-380V-50Hz
  • Evaporator: Tube Fin Heat Exchanger
  • Refrigerant: R22/R407c
  • Trademark: VENTTECH
  • Origin: Shanghai, China(Mainland)
Product Description
chilled water type fresh air handling unit Description:

1. Air cooled rooftop air conditioner.
2. Cooling capacity: 8kw to 90kw, a variety of choices.
3. High external pressure.
4. Applicable to residential and commercial buildings, hotels, and scientific research units, factories and enterprises and so on.
 
Chilled Water Air Handing Unit Spec. No. 1
Model GT-ZKW-20406080100150200250300
Air volume(m³/h)20004000600080001000015000200002500030000
Outlet air pressure(pa)300300400500500600750750750
Supply fan capacity(kw)1.11.52.245.511151518.5
Cooling4 RowsReturn air(kw)12.223.935.9486090120150179
water flow(m³/h)2.24.26.18.210.515.320.423.828.2
all fresh air(kw)2243.86290112156210265310
water flow(m³/h)3.87.71115.519.227.336.545.855
pipe diameter (DN)253240404050656580
6 RowsReturn air(kw)1730.145.26075113151188210
water flow(m³/h)2.85.37.710.513.619.225.530.236
all fresh air(kw)30.55888118150200288355420
water flow(m³/h)5.11015.220.226.235.5497072.5
pipe diameter (DN)323240405065658080
8 RowsReturn air(kw)18.335.2537090132176220264
water flow(m³/h)3.26.28.912.216.222.230.237.244.2
all fresh air(kw)34.870101138178245332410500
water flow(m³/h)5.81217.523.530.842.557.17185
pipe diameter (DN)323240405065658080
Heating2 RowsReturn air(kw)20426084108150200250300
water flow(m³/h)0.81.92.63.74.66.58.71113
all fresh air(kw)18385470100125180210280
water flow(m³/h)0.81.72.43.24.55.57.81012
pipe diameter (DN)253240404040505065
4 RowsReturn air(kw)285680110140200250320380
water flow(m³/h)1.22.43.54.86.391113.518.2
all fresh air(kw)326290125150220300380450
water flow(m³/h)1.52.73.85.46.89.513.516.219.5
pipe diameter (DN)323240404050506565
Function section
outside dimension
Mixing sectionLength(mm)500500500550600800800800800
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200
Pre-filter sectionLength(mm)100100100100100100100100100
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200
Medium efficiency filter sectionLength(mm)500500500500500500500500500
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200
Cooling coil sectionLength(mm)60060070070070080080010001000
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200
Heating sectionLength(mm)300300300400400400400400400
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200
Humidifying sectionLength(mm)400400400400400400400400400
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200
Fan sectionLength(mm)50050090040011001400160017001850
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200
Current balance sectionLength(mm)400400500900500600600600700
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200
Sound deadening sectionLength(mm)800800800500800100010001000100
Width(mm)9509501080125016001600200022002200
 Height(mm)9809801080125013201470168018802200
Air outlet sectionLength(mm)400400400800500600600800800
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200

Feature: 
1, Complying with above China Standard, which is from ARI standard. 

2, Choose best materials, main components are from China top brand or imported.

3, The modular casing design, easy interchanging each other. easy install,easy transport,easy maintaince.

4, Unique no-cold-bridge design, improve the insulation and air tightness, total air leak rate ≤2.5%;

5, With dynamic balanced double inlet Centrifugal fan, with good air dynamic features, and accurate working, high efficiency, low vibration, low noise etc. 

6, High efficient heat exchanger coil, ensure to provide the enough cooling capacity to the unit. And also high efficient breakwater panel is provided if required, water flow in coil ≤3×10-4kg/kg

7, Strong structure, good looking and permanent color.

8, Reasonable inside structure, with the suitable space for maintenance and cleaning.

9, Casing sheet: Provide double-skin construction constructing Sandwich type comprising 0.5mm thick galvanized internal and external skins and with 30mm thick polystyrene insulation of minimum 45kg/m3 density. Good airproof material is use between the casing and the frame to reduce the rate of the air leak.
The combined air handling untis are modular designed ,each modular can be used independently and can also work together and company with fan coil units to add refresh air. Not only reduce operation costs and energy saving, but also optimize air quality and create a congnitive indoor space to meet the human health requirements

Application
The units are widely used in the air system of many inductries like mechanical ,electronic, textile,medical,chemical,energy and food inductries ,etc. the units are also ideal solution for restaurants, office buildings,hospitals, theaters, supermarkets, ect.